Mitsubishi UPS Testing Exceeds Expections
The most recent Mitsubishi UPS test report from the field shows that once again, Mitsubishi UPS outperforms the competition. Marketing sheets and perfect world factory test reports are one thing; but mission critical customers deserve the true results that only field testing can provide. Mitsubishi UPS has once again exceeded expectations for efficiency, reliability, harmonics and run time.
The project specification called for a 500kVA UPS to provide 450kW @ 480volt. Reflected Harmonics should be limited to 10% and the overall AC/AC efficiency of the UPS should be at least 93%.
The test results show that the Mitsubishi 9800AE installed at this water treatment plant reflected only 3% harmonics and had an efficiency of 95%.
The client is building a new water treatment plant in the near future, and is excited to get his hands on a new Mitsubishi model, the 9900B, which should boost his efficiency to 97%.
In every case, a real-life field test is 10x as valuable as 'perfect world' factory tests. Clients need to know how their systems will perform in their facility, not in a perfect world with tests run by the marketing department. See how MonMan can help with your testing needs.