Toshiba PDU

Toshiba Power Distribution Units

Toshiba PDU Logo

 

 

 

MonMan can provide a comprehensive electrical power backup system, with Toshiba UPS, PDU, RPP and surge suppression.

Standard PDU with Data Center-grade Transformer

  • Traditional style, stand-alone PDU
  • 480V, 3 wire + G input
  • 208 / 120V 4 wire + G output
  • K1, K13. K20, TP1 and harmonic mitigating transformer options available
  • Solid copper bus construction with 200% Neutral
  • Main input circuit breaker with 120 VAC shunt trip for remote power off
  • Local EPO button
  • Premium grade cabinet with hinged exterior panels
  • Top Entry / Bottom Exit cabling standard • For top exit cabling, use sidecars (below)
  • Includes monitoring with RS-485 MODBUS output
  • Includes Square-D 42 pole NQ panelboards with 225 A main breakers
  • 2-panel models standard; 3- 6 Panel (using front and sides) possible with sidecars
  • Sidecars can face front or to the side
  • Can be fitted with panels and/or subfeed breakers

 

High Power Standard Power Distribution Center

  • “Centralized” Power Distribution Center
  • Traditional style, front-access only PDU cabinet  with up to 12 subfeed output circuit breakers
  • 480V  3 wire + G input
  • 208 / 120V 4 wire + G output
  • Solid copper bus construction with 200% Neutral
  • Main input circuit breaker with 120 VAC shunt trip for remote power off
  • Local EPO button
  • Premium grade cabinet with hinged exterior panels
  • Top and Bottom cable entry
  • Includes monitoring with RS-485 MODBUS output

Contact MonMan today about our PDU solutions!